      ASPRA validation COVID department

       

      To improve the room conditions in the Bed boxes in a Dutch Hospital COVID-19 Department, a VFA ASPRA 11010 (ASPRA Ceiling) unit was installed above the suspended ceiling. The purpose of this measure is to reduce the increased particle concentration in the room. An Induct ASPRA unit has also been placed. This is to remove the particles from the extracted air.

      The installed ASPRA units have been validated by Modderkolk Projects & Maintenance for:

      • Flow rate measurements ASPRA unit and the existing air diffusers
      • Pressure measurement
      • Particle measurement under ASPRA unit

      Below, the summary of the findings can be found. Measurements were carried out in two places.

      Bed Box Left

      Meetlocatie

      Measuring set-up discharge filter ASPRA unit

      ASPRA INduct unit

      Particle measurementReference room
      (particle count)
      Measurement under the outlet filter (position 2 working position)
      (particle count)
      0.3 μm498431.10
      0.5 μm30017.50
      1.0 μm26203.50
      3.0 μm1624.50
      5.0 μm1553.80
      10.0 μm2683.90

      Results

       

       

      Bed Box Right

      Meetlocatie

      Measuring set-up discharge filter ASPRA unit

      ASPRA INduct unit

      Particle measurementReference room
      (particle count)
      Measurement under the outlet filter (position 2 working position)
      (particle count)
      0.3 μm562845.00
      0.5 μm32913.30
      1.0 μm32277.60
      3.0 μm2966.40
      5.0 μm918.20
      10.0 μm2260.10

      Results